| AIR CONDITIONING AIR CONDITIONING - THE BASICS 1200 Moving heat from the inside to the outside 1201 Heat transfer at the inside coil 1202 Evaporator coil - collecting hot air inside the house 1203 The Freon gas goes outside 1204 Compressors - heating up Freon gas 1205 Condenser coil - exhausting hot air to the outside 1206 Hot liquid back to the house 1207 Expansion devices - cooling hot liquid Freon 1208 Air conditioning - schematic of system 1209 Latent heat of vaporization 1210 Discharging condensate 1211 High pressure and low pressure sides 1212 Inspecting the condenser unit 1213 Air conditioning - schematic of system 1214 Water-cooled air conditioning - schematic of system
AIR CONDITIONING - AIR CONDITIONING CAPACITY 1215 One ton of cooling 1216 How much area can one ton cool? 1217 Larger ducts are required for air conditioning 1218 Bigger is not better 1219 Guessing the size 1220 Measure temperature drop across inside coil
AIR CONDITIONING - COMPRESSOR 1221 Do not test when it is cold 1222 Wait before restarting a compressor 1223 Slugging 1224 Condensing unit out of level 1225 Excess electric current draw (beyond the Standards) 1226 Missing electrical shut-off
AIR CONDITIONING - CONDENSER COIL (OUTDOOR COIL) 1227 Water heater exhaust vent too close to condenser 1228 Dryer vent too close to condenser 1229 Water-cooled air conditioning - schematic of system 1230 Testing water-cooled air conditioners 1231 Missing backflow preventer
AIR CONDITIONING - EVAPORATOR COIL (INDOOR COIL) 1232 A-coil 1233 Slab coil 1234 Attic evaporator coil 1235 Coil upstream of heat exchanger 1236 Evaporator coil - inspection procedures 1237 Thermostatic expansion valve 1238 Capillary tube defects
AIR CONDITIONING - CONDENSATE SYSTEM 1239 Leaking condensate tray 1240 Attic evaporator coil 1241 Trap required in condensate line 1242 Condensate discharge locations 1243 Condensate pump
AIR CONDITIONING - REFRIGERANT LINES 1244 Refrigerant lines 1245 Filter/dryer 1246 Sight glass 1247 Leaking refrigerant lines - vulnerable areas
AIR CONDITIONING - CONDENSER FAN (OUTDOOR FAN) 1248 Condenser fan 1249 Condenser coil location requirements
AIR CONDITIONING - EVAPORATOR FAN (INDOOR FAN) 1250 Evaporator fan 1251 Belt or pulley adjustment
AIR CONDITIONING - DUCT SYSTEM 1252 General rule for duct work adequacy 1253 Flow of cooled air - older-style ductwork 1254 Flow of cooled air - modern ductwork 1255 High and low returns 1256 Testing cold air returns 1257 Ducts in concrete floor slabs 1258 Air return outside room 1259 Close humidifier damper in summer 1260 Vapor barriers and air conditioning ductwork
AIR CONDITIONING - THERMOSTATS 1261 Thermostat - bi-metallic (mercury bulb) 1262 Thermostat - bi-metallic (snap action) 1263 Poor location for thermostat
AIR CONDITIONING - LIFE EXPECTANCY 1264 Typical compressor life
AIR CONDITIONING - EVAPORATIVE COOLERS 1265 Three types of evaporative coolers
AIR CONDITIONING - WHOLE HOUSE FANS 1266 Whole house fan 1267 Whole house fan - inadequate attic venting
HEAT PUMPS HEAT PUMPS IN THEORY 1268 Heat pump principles 1269 Heat pump evaporator coil - grabbing heat from the outside air 1270 Heat pump condenser coil - giving off warm air to the inside 1271 Heat pump schematic - summer mode 1272 Co-efficient of performance (COP and balance point) 1273 Balance point 1274 All-electric heat pump system 1275 Water source heat pump - open loop system (well-based) 1276 Ground source heat pump - horizontal closed loop
HEAT PUMPS IN PRACTICE 1277 How much area can one ton cool? 1278 Triple-split system heat pump 1279 Two expansion devices 1280 Defrost cycle 1281 Poor outdoor coil location 1282 Flow of cooled air - modern ductwork 1283 Testing back-up heat 1284 Water source heat pump - open loop system (well-based) 1285 Ground source heat pump - horizontal closed loop 1286 Ground source heat pump - vertical closed loop 1287 Bivalent schematic | HEATING FURNACES - GAS AND OIL HEATING - INTRODUCTION 0700 How heat is generated 0701 British Thermal Unit (BTUs) 0702 Cool spots 0703 Cold floors 0704 The outdoor fire 0705 Fire comes inside 0706 The hole in the roof 0707 Homes built with holes 0708 Fire gets contained 0709 Building a chimney 0710 Gravity furnace 0711 House air flow 0712 The fire triangle
HEATING - HEAT TRANSFER 0713 Methods of heat transfer 0714 Electric radiant heat 0715 Insulation behind radiators 0716 Radiator covers
HEATING - GAS PIPING AND METERS 0717 Gas service line and outdoor meter 0718 Ice on regulator 0719 Poor meter locations 0720 Gas piping terminology 0721 Flexible gas appliance connectors 0722 Teflon tape at connections 0723 Flexible copper tubing for gas piping 0724 Gas shut off valves 0725 Grounding the gas piping 0726 Gas piping support 0727 Drip leg 0728 Gas service line and outdoor meter
HEATING - COMBUSTION AIR 0729 Combustion air 0730 Three kinds of draft 0731 Natural draft burners 0732 Draft hoods 0733 Backdrafting 0734 Furnace room air openings 0735 Outside air supply 0736 Backdrafting 0737 Gas burners
HEATING - GAS BURNERS 0738 Monoport burners 0739 Gas supply to burners 0740 Crossover igniters 0741 Refractory/fire pot 0742 Gas supply to burners 0743 Thermostat - bi-metallic (mercury bulb) 0744 Continuous pilot light 0745 Pilot light - relighting 0746 Scorching 0747 Heat shield or flame rollout shield
HEATING - HEAT EXCHANGERS 0748 Heat exchanger heat flow 0749 Draft hoods 0750 House air flow 0751 Exhaust breech through cold air return 0752 Heat pump coil upstream of heat exchanger 0753 Downflow and upflow furnaces 0754 Horizontal gas-fired furnace
HEATING - FURNACE CABINETS 0755 Fan cover missing 0756 Furnace covers 0757 Draft hoods 0758 Furnace clearances
HEATING - FAN / LIMIT SWITCHES 0759 Fan switch 0760 Fan/limit switch 0761 Fan/limit switch set wrong or defective
HEATING - THERMOSTATS 0762 Thermostat - bi-metallic (mercury bulb) 0763 Thermostat - bi-metallic (snap-action) 0764 Variable thermostat anticipator 0765 Thermostat must be level
HEATING - VENTING GAS FURNACES 0766 Draft hoods 0767 Vent connector slope 0768 Vent connector length 0769 Vent connector support 0770 Combustible clearances for vent connectors and B-vents 0771 Size of vent connector 0772 Chimney/vent connections 0773 Vent connector extends too far into chimney 0774 Backdrafting
HEATING - DISTRIBUTION SYSTEM 0775 House air flow 0776 Typical supply and return register locations 0777 Distribution components for forced air heating 0778 Factors affecting air supply
HEATING - BLOWERS 0779 Blowers - belt drive and direct drive 0780 Fan belts on furnace blowers
HEATING - AIR FILTERS AND CLEANERS 0781 Air filter orientation 0782 Electronic air cleaner 0783 Electronic air cleaner problems 0784 Electronic air cleaner - installed backwards/parts missing
HEATING - HUMIDIFIERS 0785 Drum-type humidifier 0786 Trickle humidifier 0787 Air flow through humidifier 0788 Humidifier above heat exchanger
HEATING - DUCT SYSTEMS, REGISTERS AND GRILLS 0789 Return ducts in floor joists 0790 Supply air registers, diffusers and grills 0791 Renovations remove ducts 0792 High and low returns 0793 Ducts in concrete floor slabs 0794 Supply and return registers poorly located 0795 Basement heat registers 0796 Return grill in furnace room 0797 Air return outside room
HEATING - MID-EFFICIENCY FURNACES 0798 Intermittent pilot light 0799 Hot surface ignition 0800 Three kinds of draft 0801 Blockage switches 0802 Improper side wall venting of gas appliances
HEATING - CONDENSING FURNACES 0803 High efficiency furnaces have long heat exchangers 0804 Condensation in high efficiency furnaces 0805 Maximizing temperature differences 0806 Venting for high efficiency furnaces 0807 Improper side wall vent locations 0808 Safety devices for high efficiency furnaces 0809 Pulse furnace - how it works 0810 Pulse furnace heat exchanger components 0811 High efficiency furnaces and duct sizes 0812 Automatic vent dampers 0813 Inspecting high efficiency furnaces 0814 Inspecting high efficiency furnaces 0815 Improper side wall vent locations 0816 Venting for high efficiency furnaces
HEATING - GRAVITY FURNACES 0817 Gravity furnaces
HEATING - COMBINATION FURNACES 0818 Combination furnace/water heater system 0819 Tempering valve - combination system
HEATING - OIL FURNACES 0820 Buried oil storage tank 0821 Exterior above ground oil storage tank 0822 Oil storage tanks - clearance from oil burner 0823 Oil storage tank leaks 0824 Underground oil storage tank 0825 Fill and vent piping 0826 Caps for fill and vent pipes on oil storage tanks 0827 Undersized fill lines 0828 Oil furnace emergency shutoffs 0829 Atomizing oil burner 0830 Oil burner with flame retention head 0831 Primary control 0832 Inspecting an oil burner 0833 Refractory/fire pot 0834 Primary control 0835 Flame sensor 0836 Barometric damper 0837 Barometric damper (draft regulator) problems 0838 Spillage from barometric damper 0839 Exhaust flue slope 0840 Exhaust flue support 0841 Exhaust flue length 0842 Exhaust flue clearances 0843 Obstruction in exhaust flue 0844 Mid-efficiency oil furnace (sidewall vented) 0845 Improper side wall vent locations for oil furnaces
HOT WATER BOILERS BOILER - INTRODUCTION 0846 How boilers work 0847 How radiators heat the air through convection 0848 Radiator covers 0849 Superheated water
BOILER - HEAT EXCHANGERS 0850 Heat exchangers 0851 Copper tube heat exchangers
BOILER - CONTROLS 0852 Pressure relief valve 0853 Pressure relief valve location 0854 Inspecting pressure relief valves 0855 High temperature limit switch 0856 Low water cut out 0857 Backflow preventer 0858 Pressure reducing valve location 0859 Backflow preventer installed backwards 0860 Temperature and pressure gauge 0861 Pressure reducing valve 0862 Combined pressure reducing valve and pressure relief valve 0863 Pressure set too low 0864 Do not operate air bleed valves 0865 Pressure reducing/relief valve installed backwards 0866 Air separators 0867 Aquastat - primary control 0868 Inoperative aquastat 0869 Pump control (combined with high limit) 0870 Zone control with pumps 0871 Zone control with valves 0872 Outdoor air temperature sensor 0873 Flow control valves
BOILER - DISTRIBUTION SYSTEMS - page 1 0874 Open hydronic system 0875 Closed hydronic system 0876 Series loop 0877 One-pipe system 0878 Two-pipe system (direct return) 0879 Two-pipe system (reverse return) 0880 Balancing methods 0881 Expansion tank water levels 0882 Overflow pipe 0883 Conventional expansion tank 0884 Diaphragm tank 0885 Circulating pump 0886 Zone control with pumps 0887 Flow control valves 0888 Pipe corrosion 0889 Extending hot water systems 0890 Covering radiators reduces efficiency BOILER - DISTRIBUTION SYSTEMS - page 2 0891 Convector 0892 Finned tube baseboard 0893 Cast iron baseboard 0894 Mixing systems 0895 Radiators on ceilings or high on walls 0896 Radiator valve leaks 0897 Do not operate air bleed valves 0898 Hot water radiant heat 0899 Water blender on radiant system 0900 Tankless coil 0901 Side arm heater 0902 Spillage switch 0903 Bypass loop
BOILER - PULSE COMBUSTION 0904 Pulse combustion - how it works
CHIMNEYS CHIMNEYS - INTRODUCTION 0950 Not required to inspect fireplace insert flue connections 0951 Chimneys 0952 Vents 0953 Chimneys are not supporting structures 0954 Warm chimneys are best 0955 Three kinds of draft 0956 Chimney extender 0957 Masonry chimneys
MASONRY CHIMNEYS - page 1 0958 Basic masonry chimney components 0959 Basic masonry chimney and fireplace components 0960 Chimney walls 0961 Lateral support for masonry chimneys 0962 Clay tile flue liners 0963 Chimney offsets 0964 Miter the flue liners 0965 Chimney clearances 0966 Chimneys supporting framing members 0967 What makes a good chimney cap? 0968 Chimney deterioration 0969 Removing abandoned chimneys 0970 Causes of chimney settling or leaning 0971 Tall masonry chimneys 0972 3-sided chimneys 0973 Bracket chimneys 0974 Flue divider missing 0975 Chimney leaning above roof line MASONRY CHIMNEYS - page 2 0976 Chimney offsets 0977 Proper chimney height 0978 Chimney height above appliance 0979 Fireplace cleanout - door too close to combustibles 0980 Incomplete liner 0981 Fire stopping 0982 What makes a good chimney cap? 0983 Rain caps and spark arresters 0984 Improper slope on cap 0985 Drip edge on cap 0986 Creosote deposits 0987 Vent connector extends too far into chimney 0988 Vent connector loose at chimney 0989 Flue or vent connector obstructed 0990 Abandoned flue openings 0991 Chimney extender 0992 Two fireplaces on one flue 0993 Two gas appliances on one flue 0994 Wood below oil on same floor level
METAL CHIMNEYS OR VENTS 0995 Type "B" vent 0996 Type "L" vent 0997 Class "A" chimney 0998 Triple-wall metal chimney 0999 650 degree C chimneys 1000 Connections of metal vent pieces 1001 Metal chimney bracing 1002 Metal chimney combustible clearances 1003 Fire stopping 1004 Missing chimney cap 1005 Rusting and/or pitting metal chimneys 1006 Chimney height 1007 Excessive offset from vertical 1008 Metal chimney not continuous through roof 1009 Adjacent chimneys of different heights
WOOD HEATING SYSTEMS WOOD HEATING - INTRODUCTION 1010 Not required to inspect fireplace insert flue connections 1011 Wood burning furnaces, boilers, fireplaces and stoves 1012 Heat content of various fuels
WOOD HEATING - FURNACES AND BOILERS 1013 Components of wood furnaces 1014 Ventilation/cooling air for wood furnaces 1015 Combustion air damper arrangement 1016 How a combustion air damper works 1017 Forced draft combustion for wood furnace 1018 Combustion chamber (firebox) 1019 Two combustion chambers 1020 Heat exchangers should not have nooks and crannys 1021 Checking the barometric damper 1022 Vent connector combustible clearances 1023 Joining vent connector sections 1024 Vent connector support and slope 1025 Thermostat conditions to watch for 1026 Fan/limit switch 1027 Duct clearances - typical 1028 Combustible return ducts 1029 Add-on wood furnace (downstream series) 1030 Add-on wood furnace (divider plate method) 1031 Wood furnace not downstream 1032 Duct arrangement allows reverse flow 1033 Dual fuel furnace (wood/oil)
WOOD HEATING - WOOD STOVES (SPACE HEATERS) 1034 Wood stove components 1035 Wood below oil on same floor level 1036 Don’t confine wood stoves 1037 Chimney liners often required for fireplace inserts 1038 Convective wood stoves 1039 Advanced combustion wood stoves 1040 Catalytic combustors 1041 Bypass damper on catalytic wood stove 1042 Pellet stoves 1043 Wood stove floor protection - masonry (legs less than 3 inches tall) 1044 Wood stove floor protection - masonry (legs 3 inches to 7 inches tall) 1045 Wood stove floor protection - steel (legs 3 inches to 7 inches tall) 1046 Wood stove floor protection - masonry (legs more than 7 inches tall) 1047 Wood stove floor protection - steel (legs more than 7 inches tall) 1048 Clearances for unlisted wood stoves 1049 Vent connector clearances 1050 Wall shields - metal 1051 Wall shields 1052 Firewood is combustible 1053 Clearance from oil tanks 1054 Wood stove vent connector slope 1055 Wood stove vent connections 1056 Draw bands or adjustable connectors 1057 Poor vent connection at chimney 1058 Wood below oil on same floor level 1059 Testing dampers
WOOD HEATING - WOOD BURNING FIREPLACES - page 1 1060 Three kinds of fireplaces 1061 Masonry fireplace components 1062 Combustible clearance requirements 1063 Basement fireplaces 1064 Problematic fireplace designs 1065 Fireplace footings 1066 Causes of chimney settling 1067 Hearth materials 1068 Metal spark strip 1069 Hearth extension dimensions 1070 Raised hearths 1071 Hearth extensions for factory built fireplaces 1072 Remove hearth extension forming boards 1073 Firebrick on walls 1074 Metal firebox clearance 1075 Flue liner should not rest on metal firebox 1076 Coal burning fireplaces 1077 Lintel rusting, sagging or loose WOOD HEATING - WOOD BURNING FIREPLACES - page 2 1078 Firebox damper 1079 Damper at top of chimney 1080 Missing damper 1081 Low damper 1082 Throat, smokeshelf and smoke chamber 1083 Smoke chamber - wall slope 1084 Smoke chamber forms must be removed 1085 Fireplace breast 1086 Settled (gap at wall) 1087 Clearance from fireplace opening 1088 Ashpit 1089 Outdoor combustion air 1090 Insulating combustion air ducts 1091 Outdoor intake screening 1092 Combustion air duct clearances 1093 Glass doors 1094 Heat circulators 1095 Gas igniters
STEAM HEATING SYSTEMS STEAM HEATING - HOW THEY WORK 1096 How steam systems work 1097 Steam system operation: at rest 1098 Steam system operation: call for heat 1099 Air vents 1100 Dimension "A" 1101 Equalizer pipe 1102 Steam system operation: thermostat is satisfied 1103 Hartford loop
STEAM HEATING - COMMON STEAM SYSTEMS 1104 One pipe counterflow system 1105 One pipe parallel flow system 1106 Two pipe system 1107 Thermostatic trap 1108 F and T trap (float and thermostat trap) 1109 Location of condensate pump 1110 Condensate pump 1111 (Not used) 1112 Location of boiler feed pump 1113 Boiler feed pump
STEAM HEATING - STEAM CONTROLS: KEEPING IT SAFE 1114 Location of low water cut-out 1115 Pressure relief valve 1116 Location of pressuretrol 1117 Hartford Loop and equalizer
STEAM HEATING - STEAM BOILER PROBLEMS 1118 Water hammer 1119 Low water cut-out for steam boiler 1120 Water level gauge 1121 Pressuretrol 1122 Hartford Loop and equalizer - details 1123 Hartford Loop - close nipple missing 1124 Air vents 1125 Main air vent 1126 F and T trap (float and thermostat trap) 1127 Condensate pump 1128 Boiler feed pump 1129 One pipe parallel flow system 1130 Two pipe system 1131 Low water cut-out for steam boiler
ELECTRIC HEATING SYSTEMS ELECTRIC HEATING -INTRODUCTION 1132 Current flow = amperage 1133 BTUs per hour compared to Kilowatts 1134 Equivalent furnaces 1135 5 to 8 watts per square foot 1136 Wire, fuse and heater sizing
ELECTRIC HEATING - SPACE HEATERS 1137 Floor mounted electric heaters 1138 Toekick electric heaters 1139 Electric wall heater - fan operated 1140 Best location for electric heaters 1141 Wiring for electric space heaters 1142 Determining baseboard heater wattage - rule of thumb 1143 Electric baseboard heaters - clearances to draperies 1144 Outlets should not be above electric baseboard heaters
ELECTRIC HEATING - ELECTRIC FURNACES 1145 Sequencers 1146 Fan limit switch 1147 Plenum heater 1148 Ampmeter testing of electric furnace 1149 Excess temperature rise
ELECTRIC HEATING - ELECTRIC BOILERS 1150 Electric boiler
ELECTRIC HEATING - RADIANT HEATING 1151 Electric radiant heat - ceilings 1152 Electric radiant heat - floors
WALL AND FLOOR FURNACES, ROOM HEATERS AND GAS FIREPLACE WALL FURNACES 1153 Wall furnace 1154 Minimum wall furnace clearances 1155 Wall furnace venting 1156 Firestop spacers 1157 Minimum vent height 1158 Wall furnace - direct vent
FLOOR FURNACES 1159 Unvented wall furnace 1160 Minimum floor furnace clearances 1161 Inspection cap missing or damaged
ROOM HEATERS 1162 Room heaters - combustible clearances 1163 Wall furnace - direct vent 1164 Unvented space heater 1165 Fireplace damper not fixed open
GAS FIREPLACES AND GAS LOGS 1166 Gas fireplace location restrictions 1167 Gas fireplace - direct vent 1168 Gas fireplace - combustible clearances |