1283 Testing Back up Heat - Heat Pumps - Heat Pumps in Practice
 
1283 Testing Back up Heat - Heat Pumps - Heat Pumps in Practice -

Image Text: Supply plenum > heating elements (typically 5 kw each) > electrical supply > indoor coil > blower > air return > Note: this test goes beyond the Standards > A: clamp the amp-meter around ONE of the main wires at the heat pump or electrical panel to check that ALL of the heating elements are working (e.g., 15 kw of auxiliary heat should draw 62.5 amps at 240 volts) > B: individual heater element lead wires can be tested to determine which one (or more) is inoperative if the overall current draw is less than expected

Powered by Phoca Gallery

AIR CONDITIONING and HEAT PUMPS, Air Conditioning Capacity, Compressor, Condenser Coil (Outdoor Coil), Evaporator Coil (Indoor Coil), Condensate System, Refrigerant, Condenser Fan (Outdoor Fan), Evaporator Fan (Indoor Fan), Duct System, Thermostats, Life Expectancy, Evaporative Coolers, Whole House Fans, Heat Pumps, Heat Pumps in Theory, Heat Pumps in Practice

­